2P 4Pole 40A 63A 500mA RCD Type B 10KA Type B RCCB for 11KW 22KW EV Wallbox
2P 4Pole 40A 63A 500mA RCD Type B 10KA Type B RCCB for 11KW 22KW EV Wallbox
Type B for all types of residual current, i.e. alternating, pulsating direct and smooth direct residual currents (IEC/ EN 62423). Direct residual currents may occur in industrial and commercial installations (and/or even in residential installations), where frequency inverters, photovoltaic power plants and other equipment with power semiconductor elements are applied.
When talking only about protective function, then the general term RCD – Residual Current Device is used. Only when specific properties or method of installation need to be characterized, a more precise term is used.
Electrical Features
Model | MIDA-100B |
Type(wave form of the earth leakage sensed) | B Type RCCB |
Rated current In | 25A ,32A ,40A,63A, 80A,100A |
Poles | 2Pole and 4Pole |
Rated voltage Ue | 2Pole: 230V / 240V , 4Pole: 400V / 415V |
Insulation voltage Ui | 500V |
Rated frequency | 50/60Hz |
Rated residual operation current(I n) | 30mA,100mA,300mA |
Rated residual making and breaking capacity (I m) | 500(In=2540A) 630(In=63A) |
Short-circuit current Inc= I c | 10000A |
SCPD fuse | 10000 |
Break time under I n | ≤0.1s |
Rated impulse withstand voltage(1.5/50) Uimp | 4000V |
Dielectric test voltage at ind.Freq. for 1min | 2.5kV |
Electrical life | 2,000 Cycles |
Mechanical life | 4,000 Cycles |
Installation
Contact position indicator | Yes |
Protection degree | IP20 |
Ambient temperature(with daily average≤35°C) | -5°C~+40°C |
Storage temperature | -25°C~+70°C |
Terminal connection type | Cable/Pin-type busbar/U-type busbar |
Terminal size top/bottom for cable | 25mm2 18-3AWG |
Terminal size top/bottom for busbar | 25mm2 18-3AWG |
Tightening torque | 2.5Nm 22In-lbs |
Mounting | On DIN rail EN60715(35mm) by means of fast clip device |
Connection | From top and bottom |
Tripping Current Range
Lagging Angle | I n>0.01A | I n≤0.01A |
0° | 0.35I n≤I≤1.4I n | 0.35I n≤I ≤2I n |
90° | 0.25I n≤I≤1.4I n | 0.25I n≤I ≤2I n |
135° | 0.11I n≤I≤1.4I n | 0.11I n≤I ≤2In |
Detectable wave form | Pulsating direct current sensitive | Surge current proof |
B class Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents,alternating residual sinusoidal currents up to 1000Hz,pulsating direct residual currents and for smooth direct residual currents,whether applied suddenly or increasing slowly. |
They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency. |
RCCB’s surge capacity. Not tripping at standardized 8/20 υs surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A. |
Circuit Diagram
Leave Your Message:
Write your message here and send it to us