2Pole 30mA 40A 63A RCD Type B Circuit Breaker DC 6mA B Type RCCB

Short Description:

Model:EKL6-100B

Rated Current: 16A, 25A,32A ,40A, 63A, 80A 100A
Poles: 2Pole (1P+N) 
Rated voltage: 2Pole: 230V/240V , 4Pole: 400V/415V
Rated frequency : 50/60Hz 
Rated residual operation current:30mA ,100mA ,300mA
Short-circuit current Inc= I c 10000A
Standard: IEC 61008-1 , IEC 62423
RCD Type B 100A 100mA DC 6mA and RCCB Type B 100A 30mA DC 6mA  
Type B RCD 100A 4Pole 2Pole 300mA for EV Charger Station

Product Detail

Product Tags

2Pole 30mA 40A 63A RCD Type B Circuit Breaker DC 6mA B Type RCCB 

Type-A and AC residual current protection devices do not detect DC residual currents and can trip spuriously or lock up, jeopardizing service continuity and putting the installation and/or personnel at serious risk.

Manufacturers of devices with power electronics, including variable-speed drives, UPS, EV charging points, etc., require type-B residual current devices to be installed to ensure their loads are properly protected.

MIDA RCD product series is widely used in building lighting lines and distribution systems as protection against powerline disconnection and conversion.

In an overcurrent event, the RCD can cut the faulty current within 0.1 seconds, protecting the operator and equipment from accidents caused by residual or leakage current.

The RCD product series is an effective short circuit protection measure for avoiding electrical hazards in the event of an installation fault, short connected circuit, overload, electric shock hazard, and over current, earth leakage current, and protection against residual current injury to personnel.

 

Item Type B RCD  /  Type B RCCB
Product Model EKL6-100B
Type B Type
Rated Current 16A , 25A , 32A , 40A , 63A , 80A ,100A
Poles 2Pole ( 1P+N )   ,   4Pole  ( 3P+N )
Rated voltage Ue 2Pole:  240V ~  ,   4Pole:  415V~
Insulation Voltage 500V
Rated frequency 50/60Hz
Rated residual operation current(I n) 30mA  , 100mA  , 300mA
Short-circuit current Inc= I c 10000A
SCPD fuse 10000
Break time under I n ≤0.1s
Dielectric test voltage at ind.Freq. for 1min 2.5kV
Electrical life 2,000 Cycles
Mechanical life 4,000 Cycles
Protection Degree IP20
Ambient temperature -5℃ upto +40℃
Storage temperature -25℃ upto +70℃
Terminal connection type Cable/Pin type busbar
U-type busbar
Terminal size top/bottom for cable 25mm² 18-3AWG
Terminal size top/bottom for busbar 25mm² 18-3AWG
Tightening torque 2.5Nm 22In-Ibs
Mounting On DIN rail EN60715(35mm)
by means of fast clip device
Connection From top and bottom 
Standard  IEC 61008-1:2010   EN 61008-1:2012
 IEC 62423:2009      EN 62423:2012